Phone
◆ Suitable for resistive and inductive loads
◆ CE certification
1 |
Load Control Element |
hyristor (SCR) Module |
2 |
Load Power Supply |
Single-phase 220V AC Three-phase 380V AC ±10% 50HZ |
3 |
Control Input |
4~20mA input, receiving impedance 120Ω |
4 |
Output Resolution |
Phase Control: 0.6°; Power Control: 20ms |
5 |
Phase Shift Range |
0~175° |
6 |
Drive Output |
1). Output: 12V pulse, variable pulse width, maximum drive current: < 30mA. Compatible with P-type SSR, integrating voltage regulation/power control functions. 2). Pulse transformer output: slotted pulse, compatible with MKK/MTC anti-parallel modules, enabling single-phase voltage regulation and full-control rectification, but without power control mode. |
7 |
LED Status Indicator |
Green: INPUT signal linear indicator light. Tricolor status lights: RUN green operation light; ALM red alarm light; STOP yellow flashing standby light。 |
8 |
Soft Start and Soft Shutdown RS for External Actuator Switch
|
No Voltage Contact Input
|
9 |
Automatic soft start and emergency stop during operation
|
Emergency stop due to overcurrent or overtemperature during operation, with the protection response time for overcurrent and overtemperature not exceeding one power cycle (20ms). |
10 |
70℃ Overtemperature Protection |
Voltage-free Normally Closed Contact |
11 |
Alarm Relay |
One set of normally open contacts (pure resistance 1A 250VAC). |
12 |
Alarm Type |
Overcurrent, Heatsink Overtemperature. |
13 |
CT Maximum Current Limit |
External 10K potentiometer, adjustment range 20% to 100%. |
14 |
Overcurrent Protection |
Adjusted by internal potentiometer P2. Reference point 1V; |